How do you calculate voltage drop?
A voltage drop calculator multiplies the current by the cable resistance over the whole loop: for single phase and DC the current runs out and back, so the length counts twice; for three phase the factor is the square root of 3 (1.732). Divide by the supply voltage for the percentage.
R is the conductor resistance at its working temperature: the 20 °C value × (1 + 0.00393 × (T − 20)) for copper, 0.00403 for aluminum. With a power factor below 1 the tool adds an approximate 0.08 Ω/km of reactance; the effect is small below about 25 mm².
What is the voltage drop of 30 m of 2.5 mm² cable at 20 A?
About 10.6 V on a 230 V supply, 4.6%, which is over the common 3% limit. 4 mm² brings it to 2.9%. The steps:
- Resistance of 2.5 mm² copper at 20 °C: 7.41 Ω/km (IEC 60228).
- At 70 °C: 7.41 × (1 + 0.00393 × 50) = 8.866 Ω/km.
- Drop: 2 × 20 A × 0.030 km × 8.866 = 10.64 V, so 10.64 ÷ 230 = 4.6%.
- With 4 mm² (4.61 → 5.516 Ω/km at 70 °C): 2 × 20 × 0.030 × 5.516 = 6.62 V, 2.9%.
The same job in American sizes: 12 AWG copper carrying 20 A for 100 feet on a 120 V circuit, at 75 °C, loses about 7.7 V, or 6.4%. 10 AWG gives about 4%; 8 AWG gets under 3%. Both examples ignore ampacity, so check that the cable can carry the current. A square root or a power is quicker on the scientific calculator than by hand.
What voltage drop is acceptable?
Three percent for the final circuit and five percent for the whole installation are the usual figures, in both the US National Electrical Code (NEC) and the British standard BS 7671, but they are not the same kind of rule. In the NEC they are informational notes, advice rather than requirements. BS 7671 sets 3% for lighting and 5% for other uses on a public supply as its recommended limits.
| Rule | Limit | On 230 V | On 120 V |
|---|---|---|---|
| NEC, branch circuit (informational) | 3% | 6.9 V | 3.6 V |
| NEC, feeder plus branch circuit (informational) | 5% | 11.5 V | 6.0 V |
| BS 7671, lighting circuits | 3% | 6.9 V | 3.6 V |
| BS 7671, other uses | 5% | 11.5 V | 6.0 V |
Source: NFPA 70 (NEC) informational notes to 210.19 and 215.2 as reported by trade references; BS 7671 Appendix 4 via NICEIC-based guidance. Check the current edition and your local rules.
Motors, sensitive electronics and long cable runs may need tighter limits, and a motor needs enough voltage at the terminals while it starts. For heat lost as power, the electricity cost calculator turns the watts shown above into a running cost.
How long can a cable run before it passes 3%?
On a 230 V single-phase supply, 4 mm² copper at 70 °C carries 20 A for about 31 meters before it passes 3%. The table shows the longest one-way run for common currents.
| Current | 1.5 mm² | 2.5 mm² | 4 mm² | 6 mm² | 10 mm² | 16 mm² |
|---|---|---|---|---|---|---|
| 10 A | 23 | 38 | 62 | 93 | 157 | 250 |
| 16 A | 14 | 24 | 39 | 58 | 98 | 156 |
| 20 A | 11 | 19 | 31 | 46 | 78 | 125 |
| 32 A | 7 | 12 | 19 | 29 | 49 | 78 |
| 40 A | 5 | 9 | 15 | 23 | 39 | 62 |
Source: calculated with this page's formula and the IEC 60228 resistances. Voltage drop only: a cable must also be rated for its current.
For feet, the length converter handles meters and feet in one step; this tool takes either unit directly.
What resistance does the calculator use?
For mm² sizes it uses the IEC 60228 class 2 maximum resistance at 20 °C, so results are on the safe side of a real cable. For AWG and kcmil it uses the wire diameter formula with annealed copper at 17.241 nΩ·m, and aluminum at 28.3 nΩ·m.
| Size | Copper | Aluminum |
|---|---|---|
| 1.5 mm² | 12.1 | n/a |
| 2.5 mm² | 7.41 | n/a |
| 4 mm² | 4.61 | n/a |
| 6 mm² | 3.08 | n/a |
| 10 mm² | 1.83 | 3.08 |
| 16 mm² | 1.15 | 1.91 |
| 25 mm² | 0.727 | 1.2 |
| 35 mm² | 0.524 | 0.868 |
| 50 mm² | 0.387 | 0.641 |
| 70 mm² | 0.268 | 0.443 |
| 95 mm² | 0.193 | 0.32 |
| 120 mm² | 0.153 | 0.253 |
| 185 mm² | 0.0991 | 0.164 |
| 240 mm² | 0.0754 | 0.125 |
Source: IEC 60228 values as tabulated by cable makers (MyCableEngineering, Bayka). Aluminum class 2 starts at 10 mm².
| Size | Area (mm²) | Ω per 1,000 ft |
|---|---|---|
| 14 AWG | 2.1 | 2.5254 |
| 12 AWG | 3.3 | 1.5882 |
| 10 AWG | 5.3 | 0.9988 |
| 8 AWG | 8.4 | 0.6282 |
| 6 AWG | 13.3 | 0.3951 |
| 4 AWG | 21.2 | 0.2485 |
| 2 AWG | 33.6 | 0.1563 |
| 1/0 AWG | 53.5 | 0.0983 |
| 2/0 AWG | 67.4 | 0.0779 |
| 4/0 AWG | 107.2 | 0.0490 |
Source: computed from the AWG diameter formula; agrees with the table in the AWG reference (14 AWG 2.525, 12 AWG 1.588, 10 AWG 0.9989). Stranded wire is a little higher.
Copper or aluminum (aluminium)?
Aluminum has about 1.66 times the resistance of copper in the same size: 1.91 against 1.15 Ω/km at 16 mm². To get the same drop, go up one or two sizes. Select the conductor in the tool and it suggests the aluminum size directly. Aluminum needs terminals rated for it.
What goes wrong with voltage drop sums?
- Using the loop length as the cable length. Enter the one-way distance; the tool doubles it.
- Forgetting temperature. A loaded cable runs hotter than 20 °C, which raises resistance by about 20% at 70 °C.
- Sizing by drop alone. A short cable can pass the drop test and still overheat; ampacity is a separate check.
- Mixing line and phase voltage. For three phase enter the line-to-line voltage, such as 400 V.
- Ignoring start-up current. Motors draw several times their running current for a moment.
Sources
- MyCableEngineering: conductor resistance (IEC 60228 class 2 values)
- Bayka: conductor resistance at 20 °C
- American wire gauge: diameter formula and resistance table
- NFPA 70, National Electrical Code
- Professional Electrician: calculating voltage drop (BS 7671 limits)
- Voltage drop (reference)
Last reviewed November 17, 2026. This calculator is for information only and does not replace the design of a qualified electrician or the wiring rules where you live. Cable figures are calculated locally in your browser. We could not open the full NEC or BS 7671 text; the limits are as quoted by the secondary sources linked above, and the 0.08 Ω/km reactance is our own approximation.